- No site calibration required
- Weatherproof IP65 rugged construction
- Easy to install
- Low cost
The Ultrasonic Level Transmitter (Plastic) utilizes the Time of Flight principle to accurately and reliably measure levels. The device offers a high measurement accuracy of ±0.5% of FS line standard and ±0.25% of FS with a beam angle and minimum dead band. It provides a measuring range of up to 15 meters. The 136 ULP features a 2-wire configuration along with keypad display and delivers a 4-20 mA output signal with optional HART communication for improved integration and diagnostics. Its robust design and reliable performance make it ideal for a wide range of water and wastewater level measurement applications.
| Specification | Details | ||||||||
|---|---|---|---|---|---|---|---|---|---|
| Display Version | With Display | ||||||||
| Measuring Range |
|
||||||||
| Beam Angle (α) | 9° | ||||||||
| Power Supply | 24 VDC @30 mA | ||||||||
| Accuracy* | ±0.5% of FS and ±0.25% of FS (On Request Contact HO) | ||||||||
| Analog Output | 2-Wire 4-20 mA | ||||||||
| Communication Interface | HART 7 or RS485 MODBUS (Optional) | ||||||||
| Keyboard / Display | LCD Display | ||||||||
| No. of Cable Entries | 02 Nos. (1/2″ NPT) or (M20×1.5) | ||||||||
| Process Connection | Threaded & Flanged | ||||||||
| Sensor Material | PP / PVDF | ||||||||
| Housing Material | ABS Plastic | ||||||||
| Ingress Protection | IP65 | ||||||||
| Ambient Temperature | 10°C to 60°C | ||||||||
| Operating Pressure | Atmospheric | ||||||||
| Humidity | 0 to 95% | ||||||||
| Installation Mounting | Top |